Submersible pumps are installed in bores and are hardly accessible for visual inspection. However, one can diagnose troubles by tuning one’s ear to the acoustical sound produced by the discharge line. This can however be done by the user rather than a trained mechanic as the frequency of sound is typical to a typical installation. It is advisable to touch one’s ear to the delivery line and observe the sound emitted by the pump. In a daily routine inspection following points should be noted:
The pump should not be operated for more than 2 Hrs. The panel must show voltage in the range of 180 V-240 V for a single phase and 350 V-440V for three phases. Any voltage outside this range is likely to harm the motor. Current drawn at different available voltages for a particular installation should be recorded and checked on a daily basis. Any abnormal current drawn by the pump set can be a possible cause of trouble. Visual discharges at the outlet of the pump will depend on various factors like voltage availability on the site, the depth of water available, and the periodic yield of the bore well.
The site safety regulations and statutory requirements if any, are to be taken care of and complied with, by the purchaser.
The motor and pump serial number, type, size, and main operating data are stamped on the nameplate of the pump set. Please quote these details while ordering the spares.
The unit is preferable to be stored in the vertical position. If the pump set is in operation and is required to be taken out for storage, after cleaning all external parts, the unit can be stored in a dry and dust-free room. Thereafter whenever re-installation is taken up, verify that the pump shaft and motor shaft rotate freely by hand. If the pump set is stored for a long time, periodic inspection is advised.
Unless otherwise contracted, our standard scope of supply is restricted to the Motor unit, Pump unit & 3 mtr. long cable only. All other accessories are to be procured by the purchaser separately.
The pump set should not be allowed to remain stationary for more than 7 days, otherwise lime, iron, and other substances tend to settle in bearings and impeller gaps. If the conditions demand that the pump set has to remain shut down for a longer period, it is recommended that the pump set should run daily for at least 15 minutes to enable it to be in a healthy condition.
If it is required to operate the pump set at the reduced discharges by throttling the delivery valve, the minimum rate of flow should not be less than 25% of the rated flow to prevent overheating of the motor.
After the goods are received at the site, they are to be verified as per the dispatch documents. Transit damages, if any are to be reported immediately to the concerned supplier. The pump and motor are packed separately, and they are packed in a corrugated tube. Great care needs to be taken while unpacking the goods, especially the motor. DO NOT PULL THE MOTOR BY ITS CABLE AT ANY TIME. After removing the equipment from the respective packing, verify that both the pump and motor shaft rotate freely.
Every pump set is supplied with 3 meters. of cable length. Since pump sets are to be installed in the bore well, an additional cable length is required for the electric supply located at ground level. The exact size of the cable is to be selected with the help of the cable selection chart.
The user is advised to use a control panel with quality accessories to avoid future problems. The control panel should have the following protective devices for the trouble-free operation of the pump set:
It is recommended to install the pump set with water level guard / dry run control of reputed make to protect the pump set against dry running at lower water levels. The water level guard consists of a cable & probe. This probe is to be installed at about 0.5 meters. above N. R. V. top. When the water level in the bore gets lowered below the probe level, the starter will get switched off automatically by the level sensing device.
Two pairs of supporting clamps are required for the installation of the pump set. One pair is required permanently to hold the pump set in position. This clamp usually rests on girders or borewell casing pipes.
It is necessary to fix a cable every 3 meters. length of delivery pipe to keep the cable in position. This minimizes the chances of damage to the cable while lowering/taking out of the pump set into/from the borewell. Care is to be taken while fixing these clips so that damage to the cable is avoided.
It is necessary to cover the borewell opening with this cap to avoid entry of any foreign material like dirty water, stones, etc. into the borewell thereby avoiding damage to the pump set. Sometimes if a larger size stone falls into the borewell and is sandwiched between the delivery pipe & borewell wall, it can damage the cable or may make it difficult to lift the pump set outside.
The pump set operating point can be adjusted using the valve, thereby avoiding the pump set operation at very low or high discharge flow.
It is recommended to protect the piping system in case of sudden power failures, causing water hammer by fitting N.R.V. in the delivery pipe.
It is recommended to fix a Bourdon tube-type pressure gauge in order to indicate the pressure developed by the pump set
Provide proper earthing to reduce the risk of electrical shock during the operation of the pump set.
A good cable connection ensures a prefect watertight joint at the same time gives reliable protection against mechanical damage to the joint. Select the proper cable size with the help of the Cable Selection Chart
To check the continuity between the three possible combinations of the power leads, connect one lead from the megger to the (R) phase and another lead from the megger to the (Y) phase of the motor cable. Rotate the handle of the megger and note down the reading. Repeat this for the (Y) and (B) phases and also for the (B) and (R) phases. In all cases, readings should be zero and the infinity value will indicate a break in the winding wire, cable, or joint or loosening of the joint, which is to be corrected.
Check the insulation resistance of winding coils and cables. Join all the leads, twist them together, and connect them to the line lead from megger; Connect another lead from the megger to clean the surface of the delivery pipe on the megger dial. The rotation of the megger handle should be enough to produce 500 volts D.C. The reading on the megger dial should never be less than 5 MΩ. A reading of 2 MΩ indicates that insulation has become weaker and (0) zero reading indicates shorting of windings/ cables or joints to the earth. In case of weaker insulation or Zero insulation, cut the cable at the lead joint and again check the insulation of winding. If it is OK, then there is no fault in winding coils, or else the motor is to be sent to the works for repairs.
Caution
Caution
Sr. No. | Date of inspection | Shut Off Pressure | Insulation Resistance Meggar | At Shut Off | On Full Discharge | ||
---|---|---|---|---|---|---|---|
Voltage | Current | Voltage | Current | ||||
– | – | – | – | – | – | – | – |
– | – | – | – | – | – | – | – |
– | – | – | – | – | – | – | – |
Coach International Technique Private Limited can supply you all the spares of your pump at reasonable price to carry out repairs at your local mechanics. However we insist that repairs to the pumps should be carried out by our authorized service stations or mechanics to save you from possible damage to your pump. Please quote the type and serial number of pump while ordering the spares of pumps.
It is better to carry out periodic checks to determine the health of Submersible Pump and possible troubles. This can be done in the following ways.
Check the insulation resistance of winding coils and cable. Join all the leads, twist them together, connect them to the line lead from megger and connect another lead from the megger to a clean surface of delivery pipe on megger dial. The rotation of megger handle should be enough to produce 500 volts D.C. The reading on megger dial should never be less than 5 Mohm. Reading of 2 Mohm indicates that insulation has become weaker and (0) zero reading indicates shorting of winding/ cables or joints to the earth. In case of weaker insulation or Zero insulation, cut the cable at lead joint and again check the insulation of winding. If it is OK, then there is no fault in winding coils or else the motor is to be sent to the works for repairs.
Don’t use extra washer in motor and pump coupling for extra play.
PUMP DOES NOT START | ||
---|---|---|
SR.No | CAUSE | SUGGESTED REMEDY |
1 | Starting panel is defective. | Replace it by new starter and check for continuity. Set relay properly |
2 | Overload protection out. | Replace it with correct rating |
3 | Fuse blown off. | Use adequate size cable. |
4 | Low line voltage | Wait until the voltage recovers or contact electricity board people. |
FUSE BLOW OFF OR CIRCUIT BREAKER TRIPS WHEN MOTOR IS STARTED | ||
---|---|---|
SR.No | CAUSE | SUGGESTED REMEDY |
1 | Defective control panel. Defective wiring. Incorrect fuse component. | Repair/ Replace as per instruction |
2 | Defective relay. | Replace and reset the starter only for checking the current drawn. Make sure that abnormal current is not drawn. |
3 | Damaged motor winding or cable. | Rewind motor / Replace cable. |
4 | Pump locked due to sand. | Remove, dismantle and clean water passages inside the pump and reassemble. |
5 | Pump set might have blocked in crossed well. | Move the unit and put straight and then start. Otherwise shaft would bend. |
6 | Pump and motor not coupled properly. | Check and realign coupling and see the freeness. |
PUMP DOES NOT DELIVER ANY WATER | |
---|---|
CAUSE | SUGGESTED REMEDY |
Water level in borewell may have gone below level of pump. | If possible lower the unit further. Stop the unit until water level rises sufficiently. Operate the pump set with throttle valve. |
Total head of the system is higher than designed head of pump set | Replace it with suitable pump set for higher head. Ensure that flow is not obstructed due to foreign bodies in valve or inferior quality of valve. |
N.R.V sand blocked / wrongly connected N.R.V on delivery pipe | Check the flow direction arrow on the N.R.V body and connect correctly. Check for sand blockage. Clean and Replace. |
Motor does not start. | Check cable connection. Check for correctness of incoming power supply. Check for backup protection. |
Motor starts but doesn’t pickup the rated speed | Check voltage / frequency. Replace cable with higher size if necessary. |
PUMP OPERATES BUT DELIVERS LESS WATER | ||
---|---|---|
SR.No | CAUSE | SUGGESTED REMEDY |
1 | Motor running lower than the rated speed. | Check voltage/ frequency. Replace cable with higher size if necessary. |
2 | Strainer / Impeller / Stage Casing may be clogged. | Dismantle the pump and clean strainer and water passage of impeller and stage casing. If necessary replace them. |
3 | Defective rising main delivery pipe (leakage) | Check the piping joints for leakage / chock. |
4 | System, resistance of the pump set is higher than estimated | Replace pipes with higher size. Replace the pump set with higher capacity |
5 | Yield of the bore is not sufficient. | Lower the unit further if possible or throttle the sluice valve adjusting to suitable flow rate. |
6 | Damaged pump parts. | Replace correct components e.g. Impeller / Diffuser / Bushes / Sleeves, Neckring etc. Check slit / sand content of . water to avoid premature wear. |
FUSE BLOWS WHEN MOTOR IS RUNNING | ||
---|---|---|
SR.No | CAUSE | SUGGESTED REMEDY |
1 | Incorrect voltage or inadequate power supply. | Stabilize the voltage to rated & wait for adequate power supply. |
2 | Overheated Overload Protection box. | Overload relay to be replaced or adjusted to a higher value. Replace starter if trips repetitively. |
3 | Defective control panel components. | Defective electrical components to be replaced. |
4 | Damaged motor cable or winding. | Check continuity in cable and wiring. Replace the cable. Rewind the motor if required. |
5 | Pump becomes sand locked | Remove, dismantle and clean water passages inside the pump. |
PUMP SET CONSUMES EXCESSIVE POWER | |
---|---|
CAUSE | SUGGESTED REMEDY |
Motor may be running at a speed higher than rated. | Check supply voltage and frequency. |
Pump set runs outside recommended range. | Ensure that pump set is operated nearer to best efficiency point. |
Thrust plate of motor worn out. | Replace / Relap it. |
EXCESSIVE NOISE AND VIBRATION IN SYSTEM | ||
---|---|---|
SR.No | CAUSE | SUGGESTED REMEDY |
1 | Excessive air or gas insertion in the water pumped. | Lower the unit further down in the borwell increasing the submergence. |
2 | Chances of water hammer in piping system especially in case of long piping. | Install a suitable N.R.V to minimize the effect of water hammer on piping system. Ensure firm support to piping along the length and specially at the bends. |
3 | Improper piping system. | Consult piping expert. |
4 | Worn out / defective bearing in motor. | Replace the bearing bush. |
CABLE SELECTION CHART FOR 100 MM. 220 VOLTS, 1Ø SUBMERSIBLE PUMP SETS | ||||||||
---|---|---|---|---|---|---|---|---|
SR.No | H.P. | MAX CURRENT IN AMPS. | CABLE SIZES IN SQ.M.M. | 1.5 | 2.5 | 4.0 | 6.0 | 10.0 |
1 | 0.35 | 3.50 | TOTAL CABLE LENGTH* IN METRE | 105 | 180 | 300 | 450 | 800 |
2 | 0.50 | 4.50 | 90 | 140 | 230 | 350 | 625 | |
3 | 0.70 | 6.00 | 60 | 105 | 175 | 260 | 460 | |
4 | 0.85 | 6.50 | 55 | 95 | 160 | 240 | 430 | |
5 | 1.00 | 7.00 | 50 | 90 | 150 | 225 | 400 | |
6 | 1.25 | 8.00 | 45 | 80 | 135 | 200 | 250 | |
7 | 1.50 | 9.00 | 40 | 60 | 105 | 155 | 275 | |
8 | 2.00 | 12.00 | 30 | 55 | 85 | 130 | 230 | |
9 | 2.50 | 14.00 | 26 | 45 | 75 | 110 | 200 | |
10 | 3.00 | 18.50 | 26 | 45 | 75 | 110 | 200 | |
11 | 5.00 | 25.00 | 40 | 50 | 60 | 100 | 220 |
CABLE SELECTION CHART FOR 100 MM.415 VOLTS, 3Ø SUBMERSIBLE PUMP SETS. | ||||||||
---|---|---|---|---|---|---|---|---|
SR.No | H.P. | MAX | CABLE | 1.5 | 2.5 | 4.0 | 6.0 | 10.0 |
1 | 0.50 | 2.00 | TOTAL CABLE LENGTH* IN METRE | 375 | 625 | 1000 | – | – |
2 | 0.70 | 2.50 | 300 | 500 | 800 | – | – | |
3 | 0.85 | 2.75 | 275 | 450 | 725 | 1090 | – | |
4 | 1.00 | 3.00 | 250 | 415 | 670 | 1000 | – | |
5 | 1.25 | 3.50 | 215 | 355 | 575 | 880 | 1500 | |
6 | 1.50 | 4.00 | 185 | 310 | 500 | 750 | 1310 | |
7 | 2.00 | 4.50 | 165 | 275 | 440 | 660 | 1155 | |
8 | 3.00 | 6.00 | 125 | 200 | 330 | 500 | 870 | |
9 | 4.00 | 8.00 | 92 | 155 | 250 | 375 | 650 | |
10 | 5.00 | 10.00 | 75 | 125 | 200 | 300 | 225 | |
11 | 6.00 | 12.00 | 55 | 90 | 145 | 200 | – | |
12 | 7.00 | 15.50 | 50 | 80 | 125 | 180 | – |
CABLE SELECTION CHART FOR 150 MM. SUBMERSIBLE PUMPSETS. | ||||||||
---|---|---|---|---|---|---|---|---|
SR.No | H.P. | MAX | CABLE | 1.5 | 2.5 | 4.0 | 6.0 | 10.0 |
1 | 2.0 | 4.5 | TOTAL CABLE LENGTH* IN METRE | 105 | 180 | 300 | – | – |
2 | 3.0 | 6.5 | 90 | 140 | 230 | – | – | |
3 | 4.0 | 8.5 | 60 | 105 | 175 | 260 | 460 | |
4 | 5.0 | 10.0 | 55 | 95 | 160 | 240 | 430 | |
5 | 6.0 | 12.0 | 50 | 90 | 150 | 225 | 400 | |
6 | 7.5 | 14.5 | 45 | 80 | 135 | 200 | 250 | |
7 | 7.5 | 14.5 | 40 | 60 | 105 | 155 | 275 | |
8 | 10.0 | 19.5 | 30 | 55 | 85 | 130 | 230 | |
9 | 12.5 | 25.0 | 26 | 45 | 75 | 110 | 200 | |
10 | 15.0 | 29.0 | – | – | 75 | 110 | 200 | |
11 | 17.5 | 34.0 | – | – | 75 | 110 | 200 | |
12 | 20.0 | 36.0 | – | – | 90 | 120 | 200 | |
13 | 25.0 | 42.0 | – | – | 90 | 120 | 200 | |
Length of cable is Measured from Pole to Motor |
CAPACITOR RATING CHART FOR SINGLE PHASE MOTOR. | |||
---|---|---|---|
SR.No | H.P. | STARTING CAPACITOR IN MFD | RUNNING CAPACITOR IN MFD |
1 | 0.35 | 120/150 | 25 |
2 | 0.50 | 120/150 | 25 |
3 | 0.70 | 120/150 | 36 |
4 | 0.85 | 120/150 | 36 |
5 | 1.00 | 120/150 | 36 |
6 | 1.25 | 150/200 | 36+25 |
7 | 1.50 | 150/200 | 36+25 |
8 | 2.00 | 200/250 | 36+36 |
9 | 2.50 | 200/250 | 36+36 |
10 | 3.00 | 250/300 | 50+50 |
11 | 5.00 | 250/300 | 50+50+50 |
Note : Due to continuous improvement in the product the information given is subject to change without prior notice. |
DISCHARGE YIELD | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
‘V’ NOTCH IN INCHES | 0.5 | 0.75 | 1.0 | 1.25 | 1.50 | 2.0 | 2.5 | 3.0 | 3.5 | 4.0 | 5.0 | 6.0 |
DISCHARGE IN LPM | 2 | 5 | 10 | 15 | 30 | 50 | 90 | 140 | 200 | 275 | 480 | 750 |
EXCESSIVE NOISE AND VIBRATION IN SYSTEM | ||
---|---|---|
Sr. No. | Cause | Suggested Remedy |
1 | Excessive air or gas insertion in the water pumped. | Lower the unit further down in the borwell increasing the submergence. |
2 | Chances of water hammer in piping system especially in case of long piping. | Install a suitable N.R.V to minimize the effect of water hammer on piping system. Ensure firm support to piping along the length and specially at the bends. |
3 | Improper piping system. | Consult piping expert. |
4 | Worn out / defective bearing in motor. | Replace the bearing bush. |
CABLE SELECTION CHART FOR 100 MM. 220 VOLTS, 1Ø SUBMERSIBLE PUMP SETS | ||||||||
---|---|---|---|---|---|---|---|---|
Sr. No. | H. P. | Max Current in Amps. | Cable Size in Sq.mm | 1.5 | 2.5 | 4.0 | 6.0 | 10.0 |
1 | 0.35 | 3.50 | Total Cable Length* in Metre | 105 | 180 | 300 | 450 | 800 |
2 | 0.50 | 4.50 | 90 | 140 | 230 | 350 | 625 | |
3 | 0.70 | 6.00 | 60 | 105 | 175 | 260 | 460 | |
4 | 0.85 | 6.50 | 55 | 95 | 160 | 240 | 430 | |
5 | 1.00 | 7.00 | 50 | 90 | 150 | 225 | 400 | |
6 | 1.25 | 8.00 | 45 | 80 | 135 | 200 | 250 | |
7 | 1.50 | 9.00 | 40 | 60 | 105 | 155 | 275 | |
8 | 2.00 | 12.00 | 30 | 55 | 85 | 130 | 230 | |
9 | 2.50 | 14.00 | 26 | 45 | 75 | 110 | 200 | |
10 | 3.00 | 18.50 | 26 | 45 | 75 | 110 | 200 | |
11 | 5.00 | 25.00 | 40 | 50 | 60 | 100 | 220 |
CABLE SELECTION CHART FOR 100 MM.415 VOLTS, 3Ø SUBMERSIBLE PUMP SETS | ||||||||
---|---|---|---|---|---|---|---|---|
Sr. No. | H. P. | Max | Cable | 1.5 | 2.5 | 4.0 | 6.0 | 10.0 |
1 | 0.50 | 2.00 | Total Cable Length* in Metre | 375 | 625 | 1000 | – | – |
2 | 0.70 | 2.50 | 300 | 500 | 800 | – | – | |
3 | 0.85 | 2.75 | 275 | 450 | 725 | 1090 | – | |
4 | 1.00 | 3.00 | 250 | 415 | 670 | 1000 | – | |
5 | 1.25 | 3.50 | 215 | 355 | 575 | 880 | 1500 | |
6 | 1.50 | 4.00 | 185 | 310 | 500 | 750 | 1310 | |
7 | 2.00 | 4.50 | 165 | 275 | 440 | 660 | 1155 | |
8 | 3.00 | 6.00 | 125 | 200 | 330 | 500 | 870 | |
9 | 4.00 | 8.00 | 92 | 155 | 250 | 375 | 650 | |
10 | 5.00 | 10.00 | 75 | 125 | 200 | 300 | 225 | |
11 | 6.00 | 12.00 | 55 | 90 | 145 | 200 | – | |
12 | 7.00 | 15.50 | 50 | 80 | 125 | 180 | – |
CABLE SELECTION CHART FOR 150 MM. SUBMERSIBLE PUMPSETS | ||||||||
---|---|---|---|---|---|---|---|---|
Sr. No. | H. P. | Max | Cable | 1.5 | 2.5 | 4.0 | 6.0 | 10.0 |
1 | 2.0 | 4.5 | Total Cable Length* in Metre | 105 | 180 | 300 | – | – |
2 | 3.0 | 6.5 | 90 | 140 | 230 | – | – | |
3 | 4.0 | 8.5 | 60 | 105 | 175 | 260 | 460 | |
4 | 5.0 | 10.0 | 55 | 95 | 160 | 240 | 430 | |
5 | 6.0 | 12.0 | 50 | 90 | 150 | 225 | 400 | |
6 | 7.5 | 14.5 | 45 | 80 | 135 | 200 | 250 | |
7 | 7.5 | 14.5 | 40 | 60 | 105 | 155 | 275 | |
8 | 10.0 | 19.5 | 30 | 55 | 85 | 130 | 230 | |
9 | 12.5 | 25.0 | 26 | 45 | 75 | 110 | 200 | |
10 | 15.0 | 29.0 | – | – | 75 | 110 | 200 | |
11 | 17.5 | 34.0 | – | – | 75 | 110 | 200 | |
12 | 20.0 | 36.0 | – | – | 90 | 120 | 200 | |
13 | 25.0 | 42.0 | – | – | 90 | 120 | 200 | |
Length of cable is Measured from Pole to Motor |
CAPACITOR RATING CHART FOR SINGLE PHASE MOTOR | |||
---|---|---|---|
Sr. No. | H. P. | Starting Capacitor in MFD | Running Capacitor in MFD |
1 | 0.35 | 120/150 | 25 |
2 | 0.50 | 120/150 | 25 |
3 | 0.70 | 120/150 | 36 |
4 | 0.85 | 120/150 | 36 |
5 | 1.00 | 120/150 | 36 |
6 | 1.25 | 150/200 | 36+25 |
7 | 1.50 | 150/200 | 36+25 |
8 | 2.00 | 200/250 | 36+36 |
9 | 2.50 | 200/250 | 36+36 |
10 | 3.00 | 250/300 | 50+50 |
11 | 5.00 | 250/300 | 50+50+50 |
Note: Due to continuous improvement in the product the information given is subject to change without prior notice. |
DISCHARGE YIELD | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
‘V’ Notch in Inches | 0.5 | 0.75 | 1.0 | 1.25 | 1.50 | 2.0 | 2.5 | 3.0 | 3.5 | 4.0 | 5.0 | 6.0 |
Discharge in LPM | 2 | 5 | 10 | 15 | 30 | 50 | 90 | 140 | 200 | 275 | 480 | 750 |